CS Instruments − FA 515 Ex

Sensor for dew point and pressure dew point measurement in potentially explosive atmospheres. Robust industrial design suitable for pressures up to 500 bar and a wide range of non-aggressive gases.

Measuring range −80…+20 °Ctd
Output 4–20 mA (2-wire technology)
Pressure range −1…500 bar
Power supply 24 VDC (18…28 VDC)
Protection IP65
ATEX approvals II 2G Ex ib IIC T4 Gb (zone 1) · II 2D Ex ib IIIC T80°C Db (zone 21)
Measuring range −80…+20 °Ctd
Output 4–20 mA (2-wire technology)
Pressure range −1…500 bar
Power supply 24 VDC (18…28 VDC)
Protection IP65
ATEX approvals II 2G Ex ib IIC T4 Gb (zone 1) · II 2D Ex ib IIIC T80°C Db (zone 21)
Standard equipment 1 · Options 1 · Accessories 5
  • FA 515 Ex – pressure dew point sensor (ATEX)Base delivery of FA 515 Ex sensor for dew point and pressure dew point measurement in potentially explosive atmospheres (4–20 mA analog output).
ParameterFA 515 Ex
Measuring range [°Ctd]−80 … +20
Output scaling−80 … +20 °Ctd = 4 … 20 mA
Pressure range [bar]−1 … 500
Power supply24 VDC (18 … 28 VDC)
Accuracy (−20 … +20 °Ctd) [°C]± 1
Accuracy (−50 … −20 °Ctd) [°C]± 2
Accuracy (−80 … −50 °Ctd) [°C]± 3
Output4 … 20 mA, 2-wire technology
Protection classIP65
EMCaccording to DIN EN 61326-1
Operating temperature (dust) [°C]−20 … +50 (II 2D Ex ib IIIC T80°C Db)
Operating temperature (gas) [°C]−20 … +70 (II 2G Ex ib IIC T4 Gb)
Storage temperature [°C]−40 … +80
Analog output load [Ω]≤ 300 at 24 V
Process connection / threadG 1/2 (stainless steel 1.4404); optional: UNF 5/8″, NPT 1/2″
Electrical connectionM12, 4-pin
Sensor protectionSinter filter 50 μm, stainless steel
Approval (ATEX – gas)II 2G Ex ib IIC T4 Gb (zone 1), intrinsically safe
Approval (ATEX – dust)II 2D Ex ib IIIC T80°C Db (zone 21), intrinsically safe
Ex supply limits (max)Ui = 28 V, Ii = 95 mA, Pi = 0.65 W

ATEX certified for hazardous areas

Certified for zones 1 (gas) and 21 (dust), compliant with ATEX II 2G Ex ib IIC T4 Gb and II 2D Ex ib IIIC T80°C Db.

Accurate pressure dew point measurement

Reliable dew point and pressure dew point measurement from −80 to +20 °Ctd for efficient residual moisture monitoring.

Suitable for high pressures up to 500 bar

Robust pressure-resistant design for high-pressure compressed air and technical gas applications up to 500 bar.

Long-term stable humidity sensor

Proven sensor with long-term stability for reliable measurements and low maintenance requirements.

4–20 mA output in 2-wire technology

Standard 4–20 mA analog output enables straightforward integration into PLC, control, and SCADA systems.

Improved electronics for higher resolution

New electronics generation provides higher signal resolution and better response at very low dew points.

Wide range of industrial gases

Suitable for compressed air and gases such as nitrogen, argon, hydrogen, biogas, and natural gas.

Industrial compressed air systems

Compressed air

Compressed air

Dew point monitoring in compressed air systems to prevent condensation, corrosion, and equipment damage, even at high pressures.

Energy systems and industrial processes

Energy

Energy

Moisture monitoring in energy and gas systems where reliable measurements and ATEX compliance are crucial for operational safety.

Process industry and dew point measurement

Process industry

Process

Used in chemical, petrochemical, and other process industries for moisture monitoring in demanding high-pressure and hazardous environments.

Contact

Quick inquiry

Send your basic details and a short project description. We usually respond within 24 hours.

Consulting and solution proposal
Delivery, installation and service
Send message
* required fields
Your message is sent directly to our email inbox.
Where to find us
Directions
Pod lipami 4 · 1370 Logatec, Slovenija