Outstanding energy efficiency
High efficiency across operating conditions: average EER above 3.4, SEER around 5 (comfort), and SEPR HT above 6.4 (process).
Air-cooled liquid chillers for process and comfort cooling, with screw compressors and R290 refrigerant.
| Nominal cooling capacity: 165–240 kW |
| Leaving water temperature: -12 °C to +25 °C |
| Outdoor temp. (full load): -20 °C to +48 °C |
| Refrigerant: R290 |
| Compressor: Screw |
| Condenser / evaporator: Microchannel / brazed plate |
| Nominal cooling capacity: 165–240 kW |
| Leaving water temperature: -12 °C to +25 °C |
| Outdoor temp. (full load): -20 °C to +48 °C |
| Refrigerant: R290 |
| Compressor: Screw |
| Condenser / evaporator: Microchannel / brazed plate |
| Parameter | ASN 050 | ASN 060 | ASN 070 |
|---|---|---|---|
| Nominalna hladilna moč (1) [kW] | 165,7 | 206 | 241,5 |
| EER (2) | 3,47 | 3,4 | 3,4 |
| SEER (3) | 4,8 | 5,07 | 5,09 |
| SEPR HT (4) | 6,42 | 6,49 | 6,49 |
| Napajanje [V / Ph / Hz] | 400 / 3 / 50 | ||
| Vezja / Kompresorji [n° / n°] | 2 / 4 | 2 / 6 | 2 / 6 |
| Glasnost (5) [dB] | 89 | 91 | 92 |
| Širina [mm] | 2230 | ||
| Globina [mm] | 2475 | 2475 | 3450 |
| Višina [mm] | 2525 | ||
| Vgrajena masa [kg] | 1489 | 1984 | 1995 |
High efficiency across operating conditions: average EER above 3.4, SEER around 5 (comfort), and SEPR HT above 6.4 (process).
Leaving water temperature from -12 °C to +25 °C and full load operation from -20 °C to +48 °C ambient for year-round use.
Optimized circuit with tandem/trio screw compressor configurations in two independent circuits for improved reliability and part-load performance.
Microchannel condenser coils and a brazed plate evaporator provide strong performance and a compact design.
Trane Symbio™ 800 adaptive controller for precise, intelligent system management and stable operation.
R290 is ozone-friendly and has an exceptionally low global warming potential.
Compact design with integrated key hydraulic and mechanical elements reduces footprint and simplifies installation; integrated hydraulic kits are also available.
The refrigerant circuit is in a separate compartment with ATEX leak detection and ATEX extraction fans; electrical cabinet is separated and safety valves are installed on low- and high-pressure sides.
Waste heat can be reused for hot-water preparation via an additional plate heat exchanger with insulation, venting, and drain.
Declared data with Eurovent certification and compliance with ErP ecodesign requirements.

Cooling tools, molds, and extruders for repeatable cycles, lower scrap rates, and better dimensional stability.

Process and equipment cooling (mixing, fermentation, packaging) with support for stable production temperatures.

Temperature stability for reactions, storage, and support systems where deviations can be critical.

Cooling emulsions, spindles, and process streams for better machining stability, tighter tolerances, and longer tool life.

Air-cooled chillers for office buildings, hotels, and technical spaces without requiring a cooling tower.

Reliable cooling for test benches, measurement processes, and prototypes where stable temperature is part of the specification.
Explore additional series and solutions available in our offer.

Robust industrial air chillers for continuous operation in demanding environments.
Več o napravi →
Energy-efficient industrial chillers using natural R290 refrigerant.
Več o napravi →
Energy-efficient cooling solutions for more demanding industrial processes.
Več o napravi →
Industrial air chillers with natural refrigerant and integrated iASN technology.
Več o napravi →Fill in a short form and we will prepare a configuration proposal based on load profile, environment, and energy efficiency goals.