Evaporator-in-tank design
A unique evaporator configuration in the hydraulic tank is developed specifically for process cooling, enabling optimized heat transfer and minimal pressure drops, even with contaminated process fluids.
Air-cooled process chillers for low-temperature glycol cooling down to −24 °C, with high reliability and stable process-fluid temperature.
| Nominal cooling capacity: 4.5–52.5 kW |
| Power supply: 400 ±10% / 3-PE / 50 Hz |
| Refrigerant: R449A |
| EER: 1.09–1.28 (depending on model) |
| SEPR (MT): 2.59–3.00 (depending on model) |
| Operating mode: Cooling only |
| Compressors: Hermetically sealed screw compressors |
| Nominal cooling capacity: 4.5–52.5 kW |
| Power supply: 400 ±10% / 3-PE / 50 Hz |
| Refrigerant: R449A |
| EER: 1.09–1.28 (depending on model) |
| SEPR (MT): 2.59–3.00 (depending on model) |
| Operating mode: Cooling only |
| Compressors: Hermetically sealed screw compressors |
| Parameter | 081 | 121 | 251 | 351 | 381 | 401 | 502 | 602 | 802 |
|---|---|---|---|---|---|---|---|---|---|
| Nominalna hladilna moč (1) [kW] | 4,54 | 9,30 | 14,10 | 17,98 | 21,17 | 25,26 | 35,23 | 41,30 | 52,49 |
| Skupna absorbirana moč (1) [kW] | 4,15 | 7,95 | 11,01 | 15,12 | 19,40 | 22,26 | 29,55 | 36,42 | 43,91 |
| EER (1) | 1,09 | 1,17 | 1,28 | 1,19 | 1,09 | 1,14 | 1,19 | 1,13 | 1,20 |
| SEPR MT (2) | 2,59 | 2,62 | 2,98 | 2,87 | 2,64 | 2,82 | 3,00 | 2,86 | 2,99 |
| Napajanje [V / Ph / Hz] | 400 ±10 % / 3-PE / 50 | ||||||||
| Raven hrupa (50 Hz) (3) [dB(A)] | 53,6 | 54,1 | 56,3 | 58,0 | 60,3 | 61,7 | 61,5 | 61,5 | 62,6 |
| Volumen rezervoarja [l] | 140 | 255 | 350 | 350 | 410 | 410 | 500 | 500 | 678 |
A unique evaporator configuration in the hydraulic tank is developed specifically for process cooling, enabling optimized heat transfer and minimal pressure drops, even with contaminated process fluids.
Operation at very low temperatures: maximum fluid inlet temperature 0 °C, minimum outlet temperature down to −24 °C, ambient temperature from −5 °C to +42 °C.
All TAEevo LWT models already meet ErP Tier 2 requirements (SEPR MT – 07/2018) for medium-temperature process chillers, ensuring high energy efficiency.
A standard oversized hydraulic tank effectively buffers sudden load variations and maintains stable process-fluid temperature.
An IP54-protected electrical panel provides reliable operation in outdoor and demanding industrial environments.
A wide range of accessories and kits allows adaptation to specific requirements of each industrial application.
The cooling circuit is designed for use in atmospheric and pressurized hydraulic systems up to 6 barg.

Reliable cooling of processes, reactors, and mixers with stable temperature during production. Also suitable for glycol applications and low leaving-temperature requirements.

Cooling of process fluids and production lines for more consistent quality and better process repeatability. Suitable for production areas where stable operating conditions and reliability matter.
Fill in a short form and we will prepare a configuration proposal based on load profile, environment, and energy efficiency goals.
Explore additional series and solutions available in our offer.

Robust industrial air chillers for continuous operation in demanding environments.
Več o napravi →
Energy-efficient industrial chillers using natural refrigerant R290.
Več o napravi →
Energy-efficient solutions for more demanding industrial processes.
Več o napravi →
Industrial chillers with natural refrigerant and integrated iASN technology.
Več o napravi →